Command FA

Command FA is used to set the content of the control register “ControlFlagsA”.

Structure

Command

Notes

CommandID

FA

Only available in Command mode

Parameter

None

Register value

HexChar

Parameter

Value

Description

None

The current value is queried

Register value

0x0000

Default value

0x0001

Service

For service use only – set to 0

0x0002

Internal

For internal use only – set to 0

0x0004

ActSW

XLC4-1 and XLC4-1A:

Activate use of Switch

(SW1 to SW2 at connector X6)

0x0008

ActVO

Activate use of VOUT

(VOUT at connector X5)

0x0010

CheckFan

Supervise Fan-valid signal

(ACNTRL at connector X5)

0x0020

Enable

ON

Activates flash function

(Signal ON at connector X6)

0x0200

Channel

control

mode

XLC4-1F4:

All channels are controlled independent from the inputs at X6

Response

fa , space , register value

General notes

The register value is applied after switching on again.

Combinations of single flags are possible.

Example with Register value

Query

Response

FA 0x000C

fa 0x000C

Activates VOUT and SW1-SW2 for cooling device.

ControlFlagA

HexChar

Reserved

Reserved

EnableON

CheckFan

ActVO

ActSW

Internal

use

Service

Description

0x0000

0

0

0

0

0

0

0

0

ON disabled, no FAN control or

external cooling device control

0x0004

0

0

0

0

0

1

0

0

ON disabled, Standard mode with

cooling device at SW1-SW2

0x0008

0

0

0

0

1

0

0

0

ON disabled, Standard mode with

Fan at VOUT

0x000C

0

0

0

0

1

1

0

0

ON disabled, VOUT and SW1-SW2

active for cooling device

0x0020

0

0

1

0

0

0

0

0

Switching XLC4 with ON-Input - no

cooling device connected

0x0024

0

0

1

0

0

1

0

0

Switching XLC4 with ON-Input -

cooling device at SW1-SW2

0x0028

0

0

1

0

1

0

0

0

Switching XLC4 with ON-Input - Fan

at VOUT

0x002C

0

0

1

0

1

1

0

0

Switching XLC4 with ON-Input -

VOUT and SW1-SW2 active for

cooling device

0x0018

0

0

x

1

1

x

0

0

Activating the fan monitoring

functions